Wire Gauge Chart

Look up AWG wire sizes from 0000 to 40. Find diameter in inches and mm, cross-section area, resistance, and max ampacity for copper wire.

AWG Wire Size Reference Table​

AWG GAUGE DIAMETER (IN) DIAMETER (MM) AREA (KCMIL) RESISTANCE (Ω/1000FT) MAX AMPS (COPPER)
0000 (4/0) 0.4600 11.684 211.6 0.0490 230
000 (3/0) 0.4096 10.404 167.8 0.0618 200
00 (2/0) 0.3648 9.266 133.1 0.0780 175
0 (1/0) 0.3249 8.252 105.5 0.0983 150
1 0.2893 7.348 83.69 0.1240 130
2 0.2576 6.544 66.37 0.1563 115
3 0.2294 5.827 52.63 0.1970 100
4 0.2043 5.189 41.74 0.2485 85
6 0.1620 4.115 26.25 0.3951 65
8 0.1285 3.264 16.51 0.6282 50
10 0.1019 2.588 10.38 0.9989 35
12 0.0808 2.053 6.530 1.588 25
14 0.0641 1.628 4.107 2.525 20
16 0.0508 1.291 2.583 4.016 13
18 0.0403 1.024 1.624 6.385 10
20 0.0320 0.812 1.022 10.15 7.5
22 0.0253 0.644 0.6424 16.14 5
24 0.0201 0.511 0.4040 25.67 3.5
26 0.0159 0.405 0.2541 40.81 2.2
28 0.0126 0.321 0.1598 64.90 1.4
30 0.0100 0.255 0.1005 103.2 0.86
32 0.0080 0.202 0.0632 164.1 0.53
34 0.0063 0.160 0.0398 260.9 0.33
36 0.0050 0.127 0.0250 414.8 0.21
38 0.0040 0.102 0.0159 659.6 0.13
40 0.0031 0.080 0.0099 1049 0.09

Quick Answer: What Is a Wire Gauge Chart?​

A wire gauge chart maps each American Wire Gauge (AWG) size to its physical and electrical properties. AWG is the standard system for sizing solid round wire in North America. A smaller AWG number means a thicker wire and a larger number means a thinner one. Engineers use the chart to pick a conductor by current load, resistance and length.

This chart uses standard AWG geometry to list: diameter in inches, diameter in mm, cross-section area in kcmil, DC resistance per 1000 ft and max ampacity for copper. It covers 26 sizes from 0000 (4/0) down to 40, and you can search and sort every column.

Common copper sizes: 4/0 = 0.4600″ / 230 A | 10 AWG = 0.1019″ / 35 A | 14 AWG = 0.0641″ / 20 A | 18 AWG = 0.0403″ / 10 A. Resistance range 0.0490–1049 Ω/1000ft.

Notes on This Chart​

  • Max amps are for copper wire in free air at 30°C ambient. Derate for bundled or enclosed runs.
  • Resistance values are for annealed copper at 20°C (68°F).
  • For aluminum wire, max amps are about 80% of copper values.
  • Always follow NEC or local code for final wire sizing.

Need precision wire and sheet metal parts?

Upload your CAD file for an instant quote. Free DFM review included with every order.

Frequently Asked Questions

What does AWG mean?

AWG stands for American Wire Gauge, a standardized system used to describe wire sizes based on diameter. In this system, lower gauge numbers indicate thicker wires, while higher numbers represent smaller wire diameters.

The AWG numbering system comes from the wire manufacturing process. Larger gauge numbers represent more drawing operations, which reduce the wire diameter. Fewer drawing steps produce thicker wires with smaller AWG numbers.

Select a wire gauge based on the required current capacity of your application. Use the ampacity rating for copper wire as a reference and choose a size that provides sufficient safety margin. For longer wire runs, consider using a larger wire gauge to reduce voltage loss.

Solid wire consists of a single conductor, making it rigid and suitable for fixed installations. Stranded wire is made from multiple smaller strands twisted together, providing greater flexibility for tight spaces and movement. Both wire types follow the same AWG sizing standard.